KENR8601 129
Troubleshooting Section
i02890172
GSC CID 0445 - FMI 12
SMCS Code: 4490-035-R7
Conditions Which Generate This Code:
The Run Relay (RR) is located within the relay
module. The GSC+P activates the RR during engine
cranking and running.
Note: Whenever the GSC+P activates or the GSC+P
attempts to activate the RR, “K5” is shown on the
lower display. When the RR is not activated, “K5” is
not shown.
The possible cause of a CID 0445 FMI 12 is an open
coil or a shorted coil of the RR.
The system responses to this fault are listed b elow.
•
If a CID 0445 FMI 12 occurs and the RR is
activated, any cus to mer’s equip ment on RM -24 of
the relay module will be disabled. The customer ’s
equipment that is connected to RM-23 will be
activated.
•
IfaCID0445FMI12occursandtheRRisnot
activated, any customer ’s equipment on RM-24
of the relay module will not be activated. The
customer’s equipment that is connected to RM-23
will remain activated.
Note: The GSC+P treats a CID 0445 FMI 12 as an
alarm fault. Active alarm faults are shown on the
display when the “Alarm Codes” key is pressed.
Also, the Engine Control Switch (ECS) must be
in any position except the OFF/R ESET position.
Clear the diagnostic code from the fault log after
troubleshooting is complete.
This troubleshooting procedure is for an active CID
0445 FMI 12 or the troubleshooting procedure is for
an inactive CID 0445 FMI 12.
Te st Step 1. CHECK T HE STATUS OF THE
DIAGNOSTIC CODE.
A. Turn the EC S to the OFF/RESET position and
then turn the ECS to the STOP position.
B. Press the “Alarm Codes” key.
C. Ob serve the upper display. Check that the CID
0445 FMI 12 is active.
D. If the diagnostic code is not active, enter the
Service Mode. View the fault log for a OP1. Check
that th e diagnostic code is in active.
Expected Result:
A CID 0445 FMI 1 2 is displayed as an active
diagnostic code or CID 0445 FMI 12 is displayed as
an inactive diagnostic code.
Results:
•
OK – The CID 0445 FMI 12 is active or the CID
0445 FMI 12 is inactive. Proceed to Test Step 2.
•
NOT OK – The CID 0445 FMI 12 has not occurred.
The diagnostic code is not active and the diagnostic
code is not inactive. STOP.
Tes t Step 2. CHECK THE INTERNAL
CABLE OF THE RELAY MODULE.
Note: Only open the relay module in a dry
environment. If the inspection and repair takes
more th an approxi mately twenty minutes replace
the desiccant bag in the GSC+P housing. Refer to
Testing And Adjusting, “Relay Module - Replace”.
A. Turn the ECS to the OFF/RESET position.
B. Disconnect the negative battery cable.
C. Temporarily, remove the relay module from the
GSC+P. Refer to Testing And Adjusting, “Relay
Module - Replace”.
D. Check the cable that attaches the relay module
to the GSC+P.
Expected Result:
The cable should be firmly seated in the connector.
The clamp should be in place. The cable should not
be damaged.
Results:
•
OK – The cable is firmly seated in the connector.
The clamp is in place. The cable is not damaged.
Reassemble the relay module to the GSC+P.
Proceed to Test Step 3.
•
NOT OK – One or more of the components are
damaged or the components are missing.
Repair: Replace the clamp if the clamp is missing.
If the cable is damaged, replace the GSC+P. Refer
to Testing and Adjusting, “EMCP Electronic Control
(Generator Set) - Replace”.
STOP.
Tes t Step 3. FUNCTIONAL CHECK OF
THE RUN RELAY IN THE OFF/RESET
POSITION
A. Turn the ECS to the OFF/RESET position.