KENR8601 33
Systems Operation Section
Options OP4 through OP11 of the Service Mode
require a p assword. Password entry reduces the
possibility of mistakenly altering info rmation. OP3
is the optio n that is used f or password entry. The
password must be correctly entered before access
isgainedtoOP4throughOP11.RefertoSystems
Operation, “Password Entry OP3”. Option OP1
and option OP2 are used for viewing information.
Option OP1 and option OP2 are not protected with
passwords.
i02898093
Fault Log Viewing OP1
SMCS Code: 4490
OP1 is the option that is used for viewing diagnostic
codes. T he fault log contains a history of the
diagnostic codes. These diagnostic codes have
occurred in the generator set system since the last
service (diagnostic code clearing). Also, the total
number of oc currences are shown on the upp e r
display. The f au lt log assists when service person n el
are troubleshooting the generator set system.
The diagnostic code c onsists of a Component
Identifier (CID) and a Failure Mode Identifier (FMI).
A “DIAG” status indicator is also shown on the
upper display. The CID informs the operator of the
component that may have failed. The FMI describes
the type of failure that has occurred. When the
diagnostic code is active the DIAG status indicator
FLASHES.
Only inactive diagnostic codes are stored in the fault
log. An active diagnostic code that is programmed
to be treated as an alarm fault becomes inactive
when the problem is no longer occurring. An active
diagnostic code that is programmed to be treated as
a shutdown fault becomes inactive when the problem
is no longer occurring AND the Engine C ontrol
Switch (ECS) is turned to the OFF/RESET position.
Active diagnostic codes are indicated when “DIAG”
is FLASHING. When the problem becomes inactive
“DIAG” is ON CONTINUOUSLY. The GSC+P stores
a maximum of 12 diagnostic codes in the fault log.
If an additional diagnostic code becomes inactive,
the GSC+P automatically clears the earliest inactive
diagnostic c ode. The GSC+P then places the new
inactive diagnostic code in the fault log.
The GSC+P autom a tica lly clears any inactive
diagnostic codes that have been stored in the fault log
longer than 750 hours. For example, if a diagnostic
code is logged at 10 hours, then the GSC+P clears
the diagnostic code w hen the hour meter is at 760
hours. If a diagnostic code is logged at 20 hours,
then the code remains logged until the hour meter is
at 770 hours. This feature prevents old diagnostic
codes from clogging the fault log, if service personnel
have forgotten t o clear the fault log after correctin g
diagnostic codes.
When an active diagnostic code changes to an
inactive diagnostic code, the GSC+P will function in
the following manner.
1. The diagnostic co de is recorded in the fault log
of the GSC+P.
2. If no other active diagnostic codes are present the
DIAG indicator will s top F LASHING and the DIAG
indicator remains on CONTINUOUSLY.
3. The fault alarm indicator that was FLASHING
turns OFF or the shutdown fault indicator that was
FLASHING turns OFF.
Procedure To View The Fault Log
Note: For a list of all diagnos tic codes, re fe r to Tes ting
And Adjusting, “Troubleshooting Diagnostic Codes”.
Note: Service Mode cannot be entered when the
ECS is in the AUTO position.
Note: Any active shutdo w n fault must be made
inactive in order to access service mode. A
FLASHING shutdown indicator indicates that a
shutdown fault exis ts. To tempor arily change a
shutdown fault from an active shutdown fault to
an inactive shutdown fault, turn the ECS to the
OFF/RESET position. To permanently change a
shutdown fault from an active shutdown fault to
an inact ive fault, the fault m ust not be occurring.
The ECS must also be turned to the OFF/R ESET
position. If the jumper that electrically connects
terminal 6 to terminal 9 is not installed on the ECS,
then the G SC+P will not power up in OFF/RESET
and any active shutdown fault must be corrected
before entering service mode.
1. Press the “SERVICE MODE” key in order to enter
Service Mode. “OP 1” is showing on the lower
display. Refer to Systems Operation, “Service
Mode”for more information.
2. Press “SELECT” key. If more than one diagnostic
code is present then th e codes be gin scrolling
on the display. The number of occurrences is
shown above the “COUNT” indicator. The lower
display shows the value from the hour m eter at
the first occurrence and the last occurrence of
each diagnostic code.
3. Press “SELECT” key. The diagnostic codes stop
scrolling.
4. Press “SCROLL RIGHT” key. If more than one
count of a diagnostic code is logged then the first
occurrence with a corresponding value from the
hour meter is showing on the lower display.
5. Press “SELECT” key. Diagnostic codes continue
scrolling.