66 KENR8601
Systems Operation Section
When an alarm fault occurs, the corresponding
indicator flashes. The indicato r flas he s at two hertz
and the horn sounds. If the alarm fault is NOT
LATCHED the indicator turns off when the alarm fault
ceases. T he h orn also turns off whe n the alarm fault
ceases. If the alarm fau lt is LATC HED, the indicator
continues to flas h until the “acknowledge/sile nce”
input is activated. Refer to Table 12for LATCHED
alarm faults as well as the indicator and horn
functions for each operating mode.
Normally, switch input (3) (terminal 10) and switch
input (4) (terminal 11) only operate indicator (7) and
indicator (8). However, switch input (3) and switch
input (4) can also operate the horn. Connect terminal
(10) (sw input 3) to terminal (3) and connect terminal
(11) (sw input 4) to terminal (4).
Alarm Silence
Activating the alarm silence switch (4) causes the
horn to cease. Also, activating the alarm silence
switch (4) causes the indicator to light continuously.
Data Link Malfunction
If th e data link malfunct ions, the indicat ors that are
controlled by the da ta link flash a t 0.5 hertz. The
indicators that are controlled by the switches function
normally.
Lamp Test
Activating the lamp test switch (3) results in sounding
thehornandturningonallindicatorscontinuouslyfor
10 seconds or until the switch is deactivated.
Mode Selection
Table 13
Mode Selection And Switch Input Connections
(1)
Input
Mode SEL1 Mode SEL2 Switch 1 Switch 2 Switch 3 Switch 4
Terminal
5
6891011
Mode
NFPA 99 Alarm
(Float) (Float)
Low Fuel Level
(Float) Spare Spare
EMCP RAN (Float) (“B-”) (Float) (“B-”) (Float) (Float)
(1)
NOTE: Connections in parentheses are req uired to s elect the mode spe cified
The annunciator module operates in one of the
two modes described in Table 13. The modes are
selected by connections made to the mode select
inputs (terminals 5 and 6) and switch (2) input
(terminal 9) as shown in Table 13.