KENR8601 43
Systems Operation Section
(Table 7, contd)
OP5-1 Setpoints
(1)
- Protective Relaying Pro g ramming
Setpoint
Name Description
Range Of Value
Factory
Default
MUIEngines:30to50,for50Hz
Gen
45 Hz
PEEC and EUI Engines: 30 to
50, for 50 Hz Gen
47 Hz
MUIEngines:36to60,for60Hz
Gen
54 Hz
PEEC and EUI En
gines: 36 to
60, for 60 Hz Gen
57 Hz
MUI Engines: 240 to 400, for 400
Hz Gen
360 Hz
P120
Underfrequency Alarm
Threshold
Frequency the GSC+P uses to issue
an underfrequency alarm.
PEEC and EUI Engines: 240 to
400, for 400 Hz Gen
378 Hz
P121
Underfrequency Alarm
Time Delay
Amount of time the GSC+P waits
beforeissuing an underfrequency
alarm.
0to120secon
ds
(2)
in increments
of 1
10
seconds
P122
Underfreque
ncy
Shutdown Enable
The GSC+P ena
bles or disables the
generator underfrequency shutdown
function.
0 - disabled
1 - enabled
1
P123
Underfrequency
Shutdown Threshold
Frequency the GSC+P uses to issue
an underfrequency shutdown.
30 to 50, for 50 Hz Gen
36 to 60, for 60 Hz Gen
240 to 400, for 400 Hz Gen
45 Hz
54 Hz
360 Hz
P124
Underfrequ
ency
Shutdown Time Delay
Amount of ti
me the GSC+P waits
before issuing an underfre quency
shutdown.
0to120seconds
(2)
in increments
of 1
15
seconds
P125 Reverse Pow
er
Shutdown Enable
The GSC+P enables or disables the
generatorreverse power shutdown
function.
0 - disabled
1 - enabled
1
P126 Reverse Power
Shutdown Threshold
Level of re
versepowertheGSC+P
uses to issue a reverse power
shutdown.
0 to 20% of n
ameplate power in
increments of 1%
15%
P127 Reverse Po
wer
Shutdown Time Delay
Amount of time the GSC+Pwaits before
issuing a reverse power shutdown.
0to30seco
nds
(2)
in increments
of 1
10
seconds
P128
Overcurrent Alarm
Enable
The GSC+P enables or disables the
overcurr
ent alarm.
0 - disabled
1 - enabled
1
P129
Phase Overcurrent
Alarm Threshold
Level of current the G SC+ P uses to
issue a phase overcurren t alarm.
100 to 160% of nameplate
current in increments of 5%
105%
P130
Phase Ove
rcurrent
Alarm Time De lay
Amount of
time the GSC+P waits
before issuing a phase overcurrent
alarm.
0to250seconds
(2)
in increments
of 1
20
seconds
P131
Total Overcurrent
Alarm Threshold
Level of current the G SC+ P uses to
issue a total ove rcurren t alarm.
100 to 160% of three times
nameplate current in increments
of 5%
105%
P132
Total Ov
ercurrent
Alarm Time De lay
Amount o
f time the GSC+P waits
before issuing a total overcurrent
alarm.
0to250seconds
(2)
in increments
of 1
20
seconds
P133
Overcurrent Shutdown
Ecable
The GSC+P enables or disables the
overcurrent shutdown.
0-disab
led
1 - enabled
1
P134
Phase Overcurrent
Shutdo
wn Threshold
Level of current the G SC+ P uses to
issue a
phase overcurrent shutdown.
100 to 160% of nameplate
curren
t in increments of 5%
110%
(continued)