KENR8601 77
Troubleshooting Section
g01436567
Illustration 52
System Schematic For A n AC Transformer Box (AT B+)
A Wye Connection Is Shown For The Generator.
When the engine-generator, or any source to
which the engine-generator is synchronized to, is
operating, voltages up to 600V are present in the
control panel.
Do not short these terminal with line voltage to
ground with any part of the body or any conduc-
tive material. Loss o f life or injury could result
from electrical shock or injury from molten met-
al.
Test Step 1. THE PROBLEM IS WITH AC
VOLTAGE OR THE PROBLEM IS WITH
AC CURRENT.
A. Determine if the problem is with AC voltage o r with
AC current. Check the display of the GSC+P while
the genset is running and the load is connected.
Results:
•
AC VOLTAGE – Zero volts are showing on the
display of the GSC+P for one or more AC phases.
Proceed to Test Step 2.
•
AC CURRENT – Zero amperes are showing on
the display of the GSC+P for one or more AC
phases.ProceedtoTestStep7.