KENR8601 63
Systems Operation Section
Note: The GSC+P diagnoses a fault in the spare
output circuit. Refer to Testing and Adjusting, “CID
448, FMI 12 Programmable Spare Relay Failed-Test”
for more information.
i02899172
Programmable Spare Output
SMCS Code: 4490
The spare output responds to a selected trigger
condition. The response is high or low. The response
and the trigger condition are programmable.
The GSC+P spare output response must be
programmedactivehighoractivelow(setpoint
SP13). An active low pulls the output down to
(“BATT-”) when the output is active. The outpu t dra ws
a maximum of 100 mA when the output is in the
low state. The active high is approximately 5.0 DCV
when no devices are connected to the spare output.
The spare output is able to drive logic circuits with a
high input impedance (36 000 ohm minimum). The
spare output w ill not drive low impedance load s such
as relays.
ThesetpointSP14mustbeprogrammedtothe
condition that triggers the spare output to the
active state. The possible trigger conditions that
can activate the spare output are listed in System
Operation, “Spare Input/Output Programming OP6”.
Refer to System Operation, “Spare Input/Output
Programming OP6” for more information on
programming the setpoints for the output.
Note: U s in g the spare output to activate the shunt trip
coil of the AC circuit breaker during engine cooldown
is common.
Note: The GSC+P diagnoses a fault in the spare
output circuit. Refer to Testing And Adjusting, “CID
334 Spare Output”.
i02899223
Programmable K ilowatt Level
Output
SMCS Code: 4490
The programmable kilowatt level output is a feature
that can be enabled by programming setpoint
P138. The programmable kilowatt level output
can be disabled by programming setpoint P138.
The p ro grammable k ilowatt level output draws a
maximum of 100 mA when the programmable kilowatt
level output is active. When the programmable
kilowatt level output is inactive, the programmable
kilowatt le ve l output is pulle d high to (“BATT + ”).
The programmable kilowatt level output (GSC+P
connector contact 34) will be activated whenever
the total power output of the generator passes
the programmed threshold (setpoint P139). This
threshold can be programmed from 0 percen t to 110
percent of the nameplate pow er (setpoint P030). A
time delay can be programmed from 0 seconds to
120 seconds (setpoint P140).
Once the programmable kilowatt level output is
activated, the programmable kilowatt level output
will be deactivated when the total power output of
the generator drops below a programmed threshold
(setpoint P141). The programmed threshold is
different from the activation threshold. The threshold
can be programmed from 0 percent to 110 percent of
the total power rating of the generator. A deactivation
time delay can be programmed from 0 seconds to
120 seconds (setpoint P140).
Refer to System Operation, “Engine/Generator
Programming OP5-0” for more information.
Note: The GSC+P diagnoses faults in the
programmable kilowa tt level output circuit. Refer to
Testing And Adjustin g, “Diagnostic Codes”.