34 KENR8601
Systems Operation Section
6. Press “EXIT” key. “OP 1” is showing on lower
display.
7. Press “EXIT” key. The display is now in normal
mode.
i02898106
Engine/Generator Setpoint
Viewing OP2-0
SMCS Code: 4490
OP2-0 is the option for viewing the engine/generator
setpoints. The engine/generator setpoints affect the
proper ope ra tion and service ability of the eng ine. The
engine/generator setpoints also affect the accuracy
of the information that is shown on the display.
The setpoints that are viewed or the setpoints
that are stored in the GSC+P should match the
specified setpoints of the particular generator set.
The setpoints are from P001 through P033 and
the setpoints are programmable. Refer to System
Operation, “Engine/Generator Programming OP5-0”.
i02898129
Protective Relaying Setpoint
Viewing OP2-1
SMCS Code: 4490
OP2-1 is the option for viewing the protective relaying
setpoints. The protective relaying setpoints determine
the respo nse o f the G SC+P when one or more of the
protective relaying functions occur. The protective
relaying functions reduce the p ossibility of da maging
the generator or the customers’ equipment. These
setpoints are from P101 through P142 and the
setpoints are programmable . F or a description of
each of these setpoints, refer to System Operation,
“Protective R e lay ing Programming OP5-1”.
i02898145
AC Factory Calibration
Setpoint Viewing OP2-2
SMCS Code: 4490
The option for the AC factory calibration setpoint
viewing is OP2-2. OP2-2 is also used for viewing
other specific data. None of these items are
programmable by service personnel.
The following information is shown on the display.
GSC+P Serial Number – The serial number of the
GSC+P ha s ten digits. T his number is unique for
each GSC+P . T he serial number is stamped o n a
label on the back of the GSC+P. The displayed serial
number w ill always match the number on the label.
GSC+P Software Level Identifier – The software
level identifier in dicates the lev el of the software that
is included within the GSC+P. The identifier h as
nine characters. “XXXXXXX-XX” is the form of the
identifier.
Setpoints P201 through P222 – These setpoints
are the AC factory calibration setpoints. The AC
factory calibration setpoints contain information that
is used during the factory calibration. These setpoints
are not programmable by service personnel.
Procedure To View The Setpoints
Note: The engine may be running or the engine
may be stopped while the operator is viewing the
setpoints.
Note: Service mode cannot be entered when the
Engine Control Switch (ECS) is in the AUTO position.
Note: An active shutdow n fault must be made
inactive in order to access service mode. To
temporarily change a shutdown fault from an active
shutdown fault to an inactive shutdown fault, turn the
ECS to the OFF/RES E T p osition. The shutdo w n fault
must be corrected, and the ECS m ust be turned to
the O FF/RESET position in order to permanently
change a shutdown fault from an active shutdown
fault to an inactive shutdown fault. If the jumper from
terminal 6 to terminal 9 is not installed on the ECS,
the GSC+P does not power up in OFF/RESET and
any active shutdown fault must be corrected before
entering service mode.
1. Press “SERVICE MODE” key in order to enter
service mode. “OP 1” is showing on the lower
display. Refer to System Operation, “Service
Mode” for more information.
2. Press “SCROLL UP” key. “OP2-0” is showing.
a. Go to Step 3 in order to v iew the setp oints that
are within OP2-0.
b. Press the “SCROLL UP” key once or press
the“SCROLLUP”keytwiceinordertoview
OP2-1 or O P2-2. The display will show OP2-1
or OP2-2. Go to Step 3.