70 SEBU8088-06
Maintenance Section
Maintenance Recommendations
Note: If electr
ical/electronic components are used
as a ground for the welder, or electrical/electronic
components are located between the welder ground
and the weld, c
urrent flow from the welder could
severely damage the component.
5. Protect the w
iring harness from welding debris
and spatter.
6. Use standard
welding practices to weld the
materials.
i02364500
Gen erator Start-u p C hecklist
SMCS Code: 44
50
Table 6
GENERATOR START-UP CHECKLIST
RATING INFORMATION
Engine Serial Number: ___________________________________
Arrangement Number: ___________________
Generator Serial Number: _________________________________
Arrangement Number: ___________________
GENERATOR NAME PLATE INFORMATION
Voltage: ___________________ Package (prime, continuous, standby): _________________
Amperage: _________________ Kilowatts: ________________________________________
Storage Location:
Main Stator Megohmmeter Reading: Before Storage: After Storage:
Generator dried for 24 hours prior to start-up? (Y/N)
Drying method:
SPACE HEATERS
Yes No
Comments
Space heaters operating properly?
Space heater operated 48 hours before
start-up?
MEGOHMMETER TEST (“SEHS9124”)
30 sec.
reading
60 sec.
reading
30 sec.
corrected
60 sec.
corrected
Ambient
temp.
Comments
Main Stator
Main Rotor
Exciter Stator
Exciter Rotor
Beginning
of Storage
PMG Stator
Main Stator
Main Roto
r
Exciter Stator
Exciter Rotor
Start-up
PMG Stator
Regulator Voltage Amps
Comments
(continued)