40 SEBU8088-06
Operation Section
Features and Controls
Synchronizati
on Mode Switch (14) – The
synchronization mode switch (14) is manually
operated. The switch has four positions: the AUTO
position, the
SEMI-AUTO position, the MANUAL
(PERMISSIVE) position, and the OFF position. Refer
to Illustration 36.
g00692931
Illustration 36
The Synchronization Mode Switch
(36) The OFF po sition
(37) The MANU A L (PER M ISSIVE ) position
(38) The A UTO position
(39) The SEMI-AUTO position
The AUTO position (6 o’clock) is used for complete
automatic paralleling. The EMCP II+P brings the
generator into sync with the bus and sends a signal
to close the motor operated breaker. The EMCP
II+P supports automatic paralleling to a dead bus.
Automatic voltage matching is not provided.
When the synchronizer mode switch is in the
SEMI-AUTO position (3 o’clock), the EMCP II+P
brings the generator into sync with the bus and holds
it there indefinitely. The operator brings the generator
online by manually closing the breaker. Automatic
voltage matching is not provided.
When the synchronizer mode switch is in the
MANUAL (PERMISSIVE) position (9 o’clock), the
operator adjusts the frequency and phase of the
generator in order to match the bus. When the
generator is in sync with the bus, the operator brings
the generator online by manually closing the breaker.
WhenthesynchronizermodeswitchisintheOFF
position (12 o’clock), all paralleling functions are
disabled.
Breaker Open Pu
shbutton/Indicator (15) – When
the generator is being taken off-line manually, the
breaker open pushbutton must be pressed by the
operator in or
der to open the breaker. When the
breaker is open and the engine is running, the
breaker open indicator (15) will light continuously.
Breaker Close Pushbutton/Indicator (16) – When
the generator is being paralleled semi-automatically
or manually,
the breaker close pushbutton must
be pressed by the operator in order to close the
breaker. The system does not allow the breaker to
close unles
s in sync. When the breaker is closed
(generator is on line), the breaker close indicator (16)
will light continuously.
Below, you can find the descriptions of the following
main modules of the EMCP II+P:
•
Generator Set Control + (GSC+)
•
Alarm Modu
le (ALM)
•
Custom Alarm Module (CAM)
Generator Set Control + (GSC+)
Functions and F eatures of the GSC+
g00634036
Illustration 37
The Locat
ion of the GSC+ on the EMCP II+P Control Panel
The left side of the control panel contains the
Generato
r Set Control + (GSC+). The GSC+ is the
main component of the system. The GSC+ displays
generator output, generator set functions, fault
conditi
ons, and key engine parameters. The GSC+
accepts information from the operator, magnetic
pickup, oil pressure sensor, water temperature
sensor,
and optional remote sources. This information
is used to determine the “ON/OFF” state of the
engine’s air, fuel, and starter.