44 SEBU8088-06
Operation Section
Features and Controls
Note: When tota
l current increases above “9999A”,
the GSC+ will show current in “kA” units.
•
Line to neutra
l voltage for all three phases at once
Upper display (29) is also used to show the various
fault codes fo
r system faults. For more information on
fault codes, see the Systems Operation, Testing and
Adjusting, RENR2484, “Electronic Modular Control
Panel II+ (EM
CP II+)”.
Note: Line to neutral voltages are not shown when
the setpoint
P032 is set to 1 for delta generator sets.
Lower displa y
The EMCP II+P lower display (31) displays the
synchronoscope. This unique display allows a
simultaneou
s visual indication of both frequency and
phase of the generator set, in reference to the bus.
Additionally, the three spare indicator lamps are used
to indicate
the synchronization status.
The lower display (31) shows values for power
metering, e
ngine parameters and the relay status.
The left side of the lower display (31) serves as a
power meter
for the generator set. The following
functions will scroll automatically.
•
Total real
power (kW)
•
Total reactive power (KVAR)
•
Percentage of rated power (%kW)
•
Power fact
or (average)
•
Total energy output (kW/h)
The display will stop scrolling when the operator
presses the power meter key for less than five
seconds. T
he display will show a particular parameter
continuously. Additional power meter functions will
scroll if the power meter key (32) is held for more
than five s
econds and then released. The additional
functions are shown below.
•
To ta l r e a
lpower(kW)
•
Real power phase A (kW)
•
Real power phase B (kW)
•
Real powe
r phase C (kW)
•
Total apparent power (kVA)
•
Total reactive power (KVAR)
•
Percenta
ge of rated power (%kW)
•
Power factor (a
verage)
•
Power factor phase A
•
Power factor phase B
•
Power factor p
hase C
•
Total energy output (kW/h)
•
Total reactive energy output (kVARHr)
Note: All real
power values are signed with a “+” or a
“−”. A negative value indicates reverse power.
Note: Real pow
er phase A, B, and C as well as
power factor phase A, B, and C are not shown when
setpoint P032 is set to 1 for delta generator sets.
Note: Total energy output that is greater than 999,999
kW/hwillbeshownasMW/hintwostepsinorderto
maintain a re
solution of 1 kW/h. The first step will
show MW/h as a whole number up to six places. The
second step will show MW/h as a decimal to three
places. For
example: 1,000,001 kW/h will be shown
as 1000 MW/h (firststep),followedby.001MW/h
(second step).
The right side of lower display (31) shows the value
of certain engine parameters. The parameters are
listed belo
w.
•
engine oil temperature (optional)
•
system battery voltage
•
engine hou
rs
•
engine speed
•
engine oil pressure
•
engine cool
ant temperature
The value for one of these conditions is shown on the
display (3
1) for two seconds. The display then scrolls
to the value for the next condition. A small pointer
identifies the engine condition that corresponds to the
value that
is showing. When the engine meter key
(34) is pressed, the lower display (31) stops scrolling.
The lower display continuously shows one particular
value. Th
e pointer flashes above the value that is
showing on the display. When the engine meter key
(34) is pressed for the second time, the lower display
will retu
rn to scrolling.