RENR9348-01 25
Troubleshooting Section
(Table 9, contd
)
System Configuration Parameters
Parameter
Available Range or Options Default
Required
Password
Fuel Filter Differential Pressure Switch
Configuration
Uninstalled
Normally Open
Normally Closed
Uninstalled Customer
Emergency Shutdown Override Switch
Installation Status
Installed or Uninstalled Uninstalled
Customer
Emergency Shutdown Override Switch
Configuration
Switch to Ground
CAN Input
Switch to
Ground
Customer
Remote Emergency Stop Switch Input Type
Configuration
Uninstalled
Normally Open
Normally Closed
Normally Open Customer
Air Intake Shutoff Detection Installation Status
Installed or Uninstalled Uninstalled
Customer
Coolant Level Installation Status Installed or Uninstalled Uninstalled Customer
System Parameters
FLS Programmed at the Factory Factory
FTS Programmed at the Factory Factory
Governor Gain Factor 0 - 65,535 16,578 Customer
Governor Minumum Stability Factor 0 - 65,535 806 Customer
Governor Maximum Stability Factor 0 - 65,535 3225 Customer
Crank Termina
te Speed 200 to 700 rpm 400
Customer
Digital Speed Control Min Speed
0to150rpm 125
Customer
Digital Speed Control Max Speed
0to150rpm 125
Customer
(1)
This parameter can be viewed only. No changes are allowed.
Parameter Worksheet
Table 10
Parameter Worksheet
Engine Parameters
Equipment ID
Engine Serial Number
ECM Serial Nu
mber
Software Group Part Number
Software Group Release Date
Software Group Description
FLS
FTS
Total Tattletale
Engine Accel. Rate
Low Idle Spe
ed
Engine Speed Droop
Droop/Isochronous Switch Enable
(continued)