194 KENR8601
Testing and Adjusting Section
(Table 30, contd)
Service Table - R
ecord Of Setpoint Values
Generator Description: Site, Serial No., EMCP II+ Part No., etc..
Setpoint Specified Value
Actual Value
(1)
Setpoint Description
Possible Values
Default Value
Spare Input/Output Programming OP6
AC05 Phase B Current
Calibration
0 to 255 bar code value
(3)
AC06 Phase C Current
Calibration
0 to 255 bar code value
(3)
AC Offset Adjustment OP10
PH A Phase A Voltage
Adjustment
−5.0to+5.0%of
measured vol
tage
0
PH B Phase B Voltage
Adjustment
−5.0to+5.0%of
measured voltage
0
PH C Phase C Volta
ge
Adjustment
−5.0to+5.0%
of
measured voltage
0
PH A-B Phase A-B Voltage
Adjustment
−5.0to+5.0%of
measured voltage
0
PH B-C Phase B-C Voltage
Adjustment
−5.0to+5.0%of
measured voltage
0
PH C-A Phase C-A Voltage
Adjustment
−5.0to+5.0%of
measured voltage
0
(1)
The actual value s pace is provided for recording and comparing valu e s during future servicing or troubleshooting of the particular
generator set.
(2)
Numerous possible values exist. See System O peration, “Spare Input/Output Programming O P 6”.
(3)
The setpoints are programmed at the factory to the calibration value which is listed on the bar code sticker of th e ATB+.
Note: This table provides a record of setpoint values
for a singular generator set. The table is intended
to be an easy reference for future servicing or
troubleshooting of a particular generator set.