188 KENR8601
Testing and Adjusting Section
Table 28
Service Table - Record Of Setpoint Values
Generator Description : Site, Serial No., EMCP II+ Part No., etc..
OP5-1 Setpoint
s
(1)
- Protective Relaying Pro g ramming
Setpoint Specified Value
Actual Value
(1)
Name
Range Of Value
Factory
Default
P101
Overvoltage Alarm
Enable
0 - disabled
1 - enabled
1
P102
Overvoltage Alarm
Threshold
100 to 125% of nameplate voltage
in increments
of 1%
105%
P103
Overvoltage Alarm
Time Delay
0 to 120 seconds
(2)
in increments
of 1
10
seconds
P104
Overvoltage
Shutdown
Enabled
0 - disabled
1 - enabled
1
P105
Overvoltage Shutdown
Threshold
100 to 125% of nameplate voltage
in increments of 1%
110%
P106
Overvoltage Shutdown
Time Delay
0 to 120 seconds
(2)
in increments
of 1
10
seconds
P107 Undervolta
ge Alarm
Enable
0 - disabled
1 - enabled
1
P108 Undervoltage Alarm
Threshold
60 to 100% of nameplate voltage
in increments of 1%
90%
P109 Undervoltage Alarm
Time Delay
0 to 120 seconds
(2)
in increments
of 1
10
seconds
P110 Undervoltage
Shutdown E nable
0 - disabled
1 - enabled
1
P111 Undervoltage
Shutdown Threshold
60 to 100% of nameplate voltage
in incremen
ts of 1%
85%
P112 Undervoltage
Shutdown Time Delay
0 to 120 seconds
(2)
in increments
of 1
15
seconds
P113
Overfrequency Alarm
Enable
0 - disabled
1 - enabled
1
P114
Overfrequency Alarm
Threshold
50 to 60, for 50 Hz Gen
60 to 70 , for
60 Hz Gen
400 to 480, for 400 Hz Gen
53 Hz
63 Hz
422 Hz
P115
Overfrequency Alarm
Time Delay
0 to 120 seconds
(2)
in increments
of 1
10
seconds
P116
Overfrequency
Shutdown E nable
0 - disabled
1 - enabled
1
50 to 60, for 50 Hz Gen
55Hz
PEEC and EUI Engines: 60 to 70,
for 60Hz Gen
66 Hz
MUI Engines: 60 to 70, for 60 Hz
Gen
63 Hz
PEEC and EUI Engines: 400 to
480, for 4
00 Hz Gen
440 Hz
P117
Overfrequency
Shutdown Threshold
MUI Engines: 400 to 480, for 400
Hz Gen
422 Hz
(continued)